Every one of these is an engine, alternator or governor fault. The machine shut down on purpose, and the useful thing you can do is write down the number.
4 Overcrank
What triggers it: Three crank attempts of 30 seconds each, 15 seconds apart, without the control sensing that the alternator had come up to frequency.
Documented causes: The set did not start: fuel supply, air-fuel mixture, wiring, starter, ignition, or the excitation circuit.
What you can do: Confirm the gas valve is open, then stop. Repeated cranking on a unit that will not start is how a good starter and a good battery are destroyed on the same night.
12 Overvoltage
What triggers it: Above 300 VAC instantly, or between 268 and 300 VAC line-to-line for three continuous seconds.
Documented causes: Connected loads, wiring connections, or the alternator windings.
What you can do: Nothing. The machine shut itself down to protect what is plugged into it, and that was the right call.
13 Undervoltage
What triggers it: Below 216 VAC line-to-line for five continuous seconds.
Documented causes: Connected loads, wiring, alternator windings, or simple overload.
What you can do: Note what was running when it happened. If it tripped as a large motor started, that is a sizing conversation rather than a fault.
14 Overfrequency
What triggers it: Above 72 Hz instantly, or between 66 and 72 Hz for six continuous seconds.
Documented causes: Governor function, fuel supply, air-fuel mixture, exhaust, the demand regulator, throttle plate, alternator windings or wiring.
What you can do: Nothing. Frequency faults are engine-speed faults and belong to a technician.
15 Underfrequency
What triggers it: Below 54 Hz on a 60 Hz set for eight continuous seconds.
Documented causes: The same list as overfrequency, plus ignition.
What you can do: Underfrequency under heavy load often means the engine is being asked for more than it has. Worth mentioning what was running.
19 Governor actuator shutdown
What triggers it: The control sensed the governor actuator circuit open or shorted.
Documented causes: Wiring connections or the actuator itself.
What you can do: Nothing.
22 Governor actuator overload
What triggers it: Maximum governor output held for ten continuous seconds.
Documented causes: Loads, wiring, fuel supply, mixture, exhaust, the actuator, ignition, high ambient temperature, or blocked cooling airflow.
What you can do: Two items on that list are yours: blocked cooling airflow and high ambient temperature. Clear anything stacked against the enclosure.
27 Voltage sense lost
What triggers it: The set is turning above 40 Hz but the control sees under 5 VAC on one or both lines.
Documented causes: Loads, alternator windings, or wiring.
What you can do: Nothing.
36 Stopped without a fault condition
What triggers it: Speed under 500 RPM and sense voltage at zero, with no other fault recorded.
Documented causes: Fuel supply, mixture, exhaust, the demand regulator, throttle plate, alternator windings, ignition, or wiring.
What you can do: Check that the gas supply is on and that nothing has changed at the meter. A set that stops cleanly with no fault has usually lost fuel.
45 Speed sense fault
What triggers it: While running, the quadrature frequency dropped to zero for one continuous second.
Documented causes: Loads, alternator windings, wiring, or open or corroded slip rings.
What you can do: Nothing.