Cummins C100D6C
Liquid-cooled · Diesel
Equipment only. Installation quoted after a free site survey.
View detailsEnclosed Diesel
100kW liquid-cooled standby generator, Diesel. Clinics, restaurants, data closets, cold storage, multi-tenant retail and small industrial.
Representative manufacturer image of the range. Enclosure finish, color and dimensions vary by model and configuration — see the specifications below for this unit.
The C100D6C is a diesel standby set in a Sound Level 1 sandstone enclosure. It weighs 3309 lb and measures 119 x 40 x 83 inches.
This configuration includes a 24-hour base fuel tank, so it runs a full day on its own supply before anyone has to arrange a fuel delivery.
Diesel gives you the highest power density and fuel you can store on site, independent of the gas utility - the usual choice when the load is large, the runtime requirement is fixed, or code requires on-site fuel.
Equipment only — installation quoted separately
The five items above are part of the installation quote, not the equipment price.
Reserve this unit — (214) 957-4307Refundable deposit · locks this price 90 days · schedules your free survey · applies 100% to final invoice
Get a free quote firstNot ready to reserve? Have us call you.
Got it. We will call you. If you would rather not wait, ring (214) 957-4307 and ask for whoever is on generators.
| Model | Cummins C100D6C |
|---|---|
| Rated output | 100 kW |
| Fuel | Diesel |
| Cooling | Liquid-cooled |
| Enclosure | Sound Level 1 enclosure, sandstone |
| Fuel tank | 24-hour base tank |
| Weight | 3309 lb |
| Dimensions (L×W×H) | 119 x 40 x 83 in |
| Voltage configurations | 120/240 1Ph |
| Extreme cold package | Available as an upgrade |
| Transfer switch | Sold separately, sized to your service |
| Application | commercial |
| Standby rating | 100 kW / 125 kVA |
| Prime rating | 90 kW / 113 kVA |
| Engine | QSB5-G13 |
| Alternator | UC3D |
| Emissions | EPA Tier 3 |
| Enclosure options | Available open, or in a Sound Attenuated Enclosure Level 1 or Level 2. A Level 1 to Level 2 upgrade kit exists. |
| Displacement | 4.5 liters (272 in³) |
| Rated speed | 1800 rpm |
| Controller | PowerCommand 2.3 |
| Certifications | NFPA 110 Level 1 compliance, FCC 47 CFR part 15 class A and B |
| Warranty | 2 year / 400 hour base warranty. 3 year and 5 year standby warranty options are available. |
This model ships in a single factory configuration.
| Part number | Voltage | Phase | Price |
|---|---|---|---|
| A063P977 | 120/240 | 1Ph | $40,704.71 |
All prices are for the equipment only.
Built in
Diesel is stored on site, so the set is independent of the gas utility entirely. For a clinic, a restaurant, cold storage or a data closet that independence is usually the whole reason for choosing diesel.
Half the engine speed of a residential air-cooled unit. Fewer revolutions per running hour is why these are specified where the set may run for days rather than minutes.
Digital governing, voltage regulation, alarm and status monitoring, with auto-shutdown on fault detection and NFPA 110 Level 1 compliance.
Diesel degrades, absorbs water and grows biological contamination if it sits. A set that runs rarely needs its fuel maintained, not just topped up — which is part of what a service visit covers.
Accessories and maintenance parts for this unit →
Specifications on this page are taken from the Cummins published specification sheet for
the air-cooled Connect range.
Download it from Cummins →
Pairs with
The switch is sized to your electrical service, not to the generator. These are the families that typically apply at this output — we confirm the exact one at the survey.
The C100D6C equipment price is $40,704.71. Installation on a 100kW diesel unit varies too widely to band honestly - the pad, the fuel supply, the switchgear and the electrical service are all engineered to the specific site. We quote it in writing after a site survey, and we will tell you the drivers before we quote so you can see where the money goes.
Commercial standby power for facilities with substantial motor and HVAC load. Final confirmation comes from a load calculation against your actual panel, which we do at the survey.
Yes. A standby generator cannot be code-compliantly connected without an automatic transfer switch - it is what keeps your generator from backfeeding the utility line and endangering line crews. The switch is sized to your electrical service, not to the generator, so we confirm your service size at the survey before specifying it.
Availability changes weekly. A refundable deposit reserves a specific unit and locks the equipment price for 90 days, which is the practical way to hold one while the survey and permit work happen. If we cannot source it in a reasonable window, you get the deposit back.
Compare
Liquid-cooled · Diesel
Equipment only. Installation quoted after a free site survey.
View details
Liquid-cooled · Diesel
Equipment only. Installation quoted after a free site survey.
View details
Liquid-cooled · Diesel
Equipment only. Installation quoted after a free site survey.
View detailsEquipment is $40,704.71. The installation number depends on your property, and the only honest way to get it is to come look. That visit is free.